Permit Number: TC-RES-0325-01356
Parcel: 113050420

Address:
3508 N OLSEN AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0325-01356
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2025 Residential Building - Standard APPROVED Submit the completed Special Inspection Certificate with part C stamped once the inspection for the field welding is complete. Please attach a letter or report of the field welding along with the completed SIC. You can submit this as a deferred submittal.
11/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/04/2025 Residential Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0325-01356
3508 N OLSEN AV. – RX-2
Detached Carport (2nd Review)

TRANSMITTAL DATE: November 4, 2025

Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. This comment was not addressed correctly. Per Construction Plan I-671, sheet I-671_002, found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-671, the distance from centerline of Olsen to the face of curb should be 18’ and from face of curb to the west property line should be 12’. Provide a dimension from the center line of Olsen to the face of curb, and from face of curb to the property line.

2. Per UDC Table 6.3-1.A the minimum setback is twenty feet facing each interior property line, proposed setback is 6.7’. The DDO must be approved by all review agencies prior to Zoning approval.

3. Based on your response to comments you are now proposing to attach the carport to the dwelling. Clearly demonstrate that the connection is a minimum 5’-0” wide and can support a 20 lb live load.

Additional comments may be forthcoming once the comments are addressed correctly.

DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov”.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/07/2025 Zoning Modifications - DDO - Standard REQUIRES RESUBMIT Address the following comments and re-submit the application as a new sub-record under this permit by locating your existing permit by selecting “My Work”. Select the “Sub-Records” tab and then select “Zoning Modification”.
Comments:
1. Required and proposed setback is not correct according to the plan. The required is 20' to the south lot line, proposed is 6.7'.
2. Provide the signed letter of authorization for the DDO application.
If you have any questions, email Mark.Castro@tucsonaz.gov
10/07/2025 PDSD Application Completeness Express REVIEW COMPLETED