| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/14/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-0325-01321 ADDRESS/PARCEL: (8662 E PLACITA DE LAS TARASCAS TUCSON, AZ 85710) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. The submitted plans are missing required information: a. Electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the EV charging load (Include the EV charger in the load calculations as a continuous use item). See 2018 IRC E3704.2. b. Wiring methods, circuiting information such as conductor size and type, conduit size and type, and breaker size c. Provide GFCI protection for the new EV charging receptacle per NEC 625.54 2. Please resubmit |
||
| 03/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |