Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0325-01142 (5531 E MILES CI TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
2. The 1” pipe is undersized for the given, and future loads show. 1” pipe max capacity at 110’ feet is 173,000 btuh. With the possibility of the kitchen being added, the 1” pipe is undersized.
3. The ½” pipe to the furnace is undersized for the given demand and pipe length, 90’, 60,000 btuh.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov