| 05/28/2024 | Site Zoning | APPROVED | |||
| 05/29/2024 | Site Engineering | NOT REQUIRED | |||
| 05/29/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/13/2024 | Residential Building | REQUIRES RESUBMIT | Show compliance with the 2018 IRC building code. Provide a cross-section detail for the new exterior wall, R106.1.1. Show exterior wood siding with a 6” clearance above the ground (R317.1 item 5) or 2" above exterior concrete surfaces. Show the method of anchoring treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem where the floor is less than 6” above grade. | ||
| 04/29/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |