Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0324-01797
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/19/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0324-01797 (2423 E CAMERON VISTA TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Provide Sub panel taps in compliance with NEC 705.12*; 705.12(B)(2)(3) b Busbars.) 120% bus bar rule, backfeed at the opposite side of the bus bar 2. Provide back-fed breaker sized per the provided calculations. 3. The #2AL conductor is undersized for the given load, E3603.1.1. Service Conductors shall have an ampacity of not less than 83% of the service rating. Service rating is 125A. 125*.83 = 103.75A. Ampacity of #2AL is 90A which is less than the service rating calculation. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
09/05/2024 | PDSD Application Completeness | REVIEW COMPLETED |