04/22/2024 Site Zoning APPROVED
04/19/2024 Site Engineering NOT REQUIRED
04/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/08/2024 Residential Building REQUIRES RESUBMIT 1. Show an individual water heater for each building, P2801.1. Clarify the location at the building being supplied service as a carport is not show on the site plan.
2. The building shall be supplied by a single service, NEC 230.2 & E3601.2. Show all loads assigned to panel B in the load calculation and upgrade the feeder size as appropriate.
3. Provide a panelboard clear working space of 30” wide x 36” deep for panel B, E3405.2.
03/21/2024 PDSD Application Completeness Express REVIEW COMPLETED