Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0324-01650
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/19/2024 | Site Engineering | NOT REQUIRED | |||
04/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/28/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | TC-RES-0324-01650 Resubmit comment Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. Per manufactures instructions the maximum AC protection is 20A per branch circuit. The maximum units per branch is limited to 13. Limit 13 per branch per manufacturer not 20. 2. Show where Tag 3 will be on electrical line diagram. 3. Provide Tag 4 information on wire schedule, sheet PV-03. For any questions contact: building_official@tucsonaz.gov |
||
03/20/2024 | PDSD Application Completeness | REVIEW COMPLETED |