03/19/2024 PDSD Application Completeness Express REQUIRES RESUBMIT Resubmit with the following:
1. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, and showing the new stove circuit OCPD, E3404.13 & E3706.2.
2. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4. Provide the Stove conductor size and type, and the OCPD protecting the conductor.