Permit Number: TC-RES-0324-01614
Parcel: 117030180

Address:
847 N 2ND AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0324-01614
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/20/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0324-01614 (847 N 2ND AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Show sub-panel feeder conductor and conduit sizes with appropriate correction factors, E3705. Also provide the sub-panel OCPD at the source, E3705.5.
2. Feeder Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4.
3. Aerial views of the property show the overhead service conductors passing over the roof of the structure. The overhead service conductor over the structure requires an 8’ clearance above the roof, E3604.2.1. The 8’ clearance is required to maintained for a distance of 3’ from the edge of the roof. Verify this clearance is met, or Show a mast height necessary to achieve this clearance. The necessary mast height at the existing panel location may not be a feasible installation and may require the relocation of the service entrance to a code compliant location.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/20/2024 PDSD Application Completeness REVIEW COMPLETED Per customer this is a meter pack.