Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0324-01583
Parcel: 221080510

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0324-01583
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/18/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0324-01583 (4867 W RED WOLF DR TUCSON, AZ 85742)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).


1. Show Combination ARC Fault protection for all circuits listed in E3902.16. All Arc Fault circuit interrupters shall be installed in readily accessible locations, E3902.15.
2. Clothes Washer and laundry area GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.
3. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4. Circuit 14 can only supply the outlet receptacles for the two bathrooms. It cannot supply any other outlets for other equipment.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/18/2024 PDSD Application Completeness Express REVIEW COMPLETED