Permit Number: TC-RES-0324-01508
Parcel: 126131180

Address:
4620 E 14TH ST

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-RES-0324-01508
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/22/2025 Other Inspection Reports (Deferred Submittal) Express REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0324-01508
ADDRESS/PARCEL: (4620 E 14TH ST TUCSON, AZ 85711)
Submit your revised reports along with a response letter which states how all Building Review Section comments were addressed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Based on the provided manual J, the proposed dual 3.5 ton A/C units are almost double the required cooling capacity for the structure. Per the manual J, zone one requires a 1.5 ton unit, and zone 2 requires a 2.5 ton unit, for a total tonnage of 4. A redesign of the mechanical plans is needed to more closely align with the results of the manual J. Below are two different options that could be explored.
2. Correct the mechanical plans to show the correct unit sizing per zones 1&2 of the manual J.
3. Keep one of the 3.5 ton units and show a redesign of the ductwork to support a smaller 1-1.5 ton second unit.
4. Please resubmit.
Should you have any questions about these comments, I can be reached at ian.gillaspie@tucsonaz.gov.
08/20/2025 PDSD Application Completeness Express REVIEW COMPLETED