Permit Number: TC-RES-0324-01448
Parcel: 136237870

Address:
2976 S VAUGHN DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.3

Permit Number - TC-RES-0324-01448
Review Name: RESIDENTIAL SOLAR v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/17/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT The #8 AWG conductor, between the disconnect and MSP, is undersized for the given OCPD (60A). Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4.
Building_Official@tucsonaz.gov
04/15/2024 PDSD Application Completeness Express REVIEW COMPLETED