Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.3
Permit Number - TC-RES-0324-01448
Review Name: RESIDENTIAL SOLAR v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/17/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
04/17/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | The #8 AWG conductor, between the disconnect and MSP, is undersized for the given OCPD (60A). Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4. Building_Official@tucsonaz.gov |
||
04/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |