Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0324-01447
Parcel: 106071370

Address:
3302 N RENO AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0324-01447
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0324-01447 (3302 N RENO AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide a panel schedule, clearly labeled for both the main panel and the sub panel, showing wire size of each circuit or notate the wire size for each protection rating, E3702.2. Provide the actual OCPD size being used and show conductors sized correctly.
2. Use Table E3705.1, 60 degree C column, for sizing branch circuits and conductors rated at 100 AMP or less, E3705.4.1.
3. OCPD for copper conductor may not exceed 15A for #14, 20A for #12 or 30A for #10 rating as required by E3705.5.3 and NEC 240.4(D)(small conductors).
4. Show the sub-panel feeder size and over-current protection (breaker size) in the main panel schedule, E3705.5.
5. Show overcurrent protection not exceeding the allowable conductor ampacity, E3705.5.
6. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8. GFCI
7. Show one 20 AMP branch circuit for the dishwasher/disposal; this circuit may not serve other locations, E3703.8 City of Tucson Amended. GFCI
8. Show all receptacle outlets located outdoors, garages or carports at grade level and within 6’ of a wet bar or sink with ground fault circuit interrupting protection, E3902.
9. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, and bathrooms) including receptacles, lights and smoke detectors require combination type arc-fault circuit interrupters, E3902.16


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/22/2024 PDSD Application Completeness Express REVIEW COMPLETED