Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0324-01373
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/07/2025 | Residential Building | REQUIRES RESUBMIT | TC-RES-0324-01373 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections. Note the 2018 IRC reference on the plans. Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files. SITE PLAN: 1. Show the location of the electrical panel, R106.1.1. SECTIONS - DETAILS: 1. A roof projection may not extend closer than 24” to the adjoining (neighboring) property line, R302.1 (City of Tucson Amended). Remove the roof overhang near the west property line. MECHANICAL PLANS: 1. Show the exterior HVAC unit within the property line, 106.1.1. ELECTRICAL PLANS: 1. Show a wall switch controlled light at outdoor entrances, E3903.3. If you have any questions, please contact: PDSD-Residential@tucsonaz.gov City of Tucson Residential Plan Review Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services ---------------------- |
||
| 12/30/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |