Permit Number: TC-RES-0324-01373
Parcel: 138142060

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0324-01373
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2024 Fire New Construction NOT REQUIRED
04/05/2024 Site Engineering NOT REQUIRED
04/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2024 Residential Building REQUIRES RESUBMIT 1. A roof projection may not extend closer than 24” to the neighboring property line, R302.1 (City of Tucson Amended). Remove the west roof overhang from the Rear Elevation.
2. Both standard and high-density R-30 batt insulation requires a space greater than provided with 2” x 8” framing, N1102.1. Identify the products that provide the intended minimum R-30 total value for an addition less than 500 SF, R806.5.
04/08/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0324-01373
109 W CALLE MARGARITA – R-1/R-2
Office Addition (1st Review)

TRANSMITTAL DATE: April 8, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence with an accessory dwelling Unit (ADU) is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, 8, & 9 and 6.6.3.

.
1. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. The minimum setback to the west property line is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on wall height of less than 9’-0’ the required perimeter yard setback from the office addition is 6’-0”, proposed setback is 2’-0”. To reduce the perimeter yard setbacks a Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
04/25/2024 Zoning Modifications - DDO REQUIRES RESUBMIT DATE: 4/25/24
FROM: Georgia Pennington, Planner

COMMENTS:

1. Zoning has identified an item that requires a Design Development Option (DDO). The DDO application and requirements may be retrieved from: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/planning-amp-zoning/ddo_for_setback_and_height_udc.pdf The completed application shall be submitted as a PDF under assigned permit number TC-RES-0324-01373.

If you have questions about this transmittal, please email me at georgia.pennington@tucsonaz.gov.
03/08/2024 PDSD Application Completeness Express REVIEW COMPLETED
03/19/2024 Site Landscape REVIEW COMPLETED