Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0324-01309
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2024 | Site Zoning | APPROVED | |||
| 04/04/2024 | Site Engineering | NOT REQUIRED | |||
| 04/08/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/18/2024 | Residential Building | REQUIRES RESUBMIT | 1. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. 2. Show interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors with combination type arc-fault circuit interrupters, E3902.16 & 17. |
||
| 03/07/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |