Permit Number: TC-RES-0324-01304
Parcel: 140103060

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0324-01304
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2024 Site Engineering NOT REQUIRED
04/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/19/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Mobil/Manufactured Homes require an analysis and seal of an Arizona Registered Registrant for verifying the structure can support the additional loads associated with a PV installation. Provide the engineer structural letter of the complete roof framing information for determining load carrying capacity for the roof structure. Show all load bearing locations. Demonstrate the ability for supporting the existing and additional dead load, and provide an engineer’s calculation, design, and seal for verifying the truss load carrying capacity. R324.4 Equipment shall be positively attached to the roof structure with a minimum of one connection per 10 sf of equipment (minimum of two connections per piece of equipment). Point loads exceeding 40 lbs shall require a structural load analysis by licensed Arizona engineer. R106.1 and R301.1.3
Building_Official@tucsonaz.gov
03/05/2024 PDSD Application Completeness REVIEW COMPLETED