Permit Number: TC-RES-0323-03971
Parcel: 10408055C

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-RES-0323-03971
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/25/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 A written response could not be located in the re-submittal.

2 This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration ules R4-30-304.

3 Include load calculations as requested for the Distribution panel and EV panel. As well as the manufacturer cut sheets of the EV Charger pedestals.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. Include load calculations as requested for the Distribution panel and EV panel.