Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/02/2025 Residential Building REQUIRES RESUBMIT TC-RES-0323-03970
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans.

Clarify the existing or completed construction which was inspected while T07CM00673 was active and the proposed construction.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement.
2. Show the square footage of living space, garage, and covered structures, R106.1.1.

PLANS:

1. Remove and replace illegible notes.
2. Show the functional name of each room, R106.1.1. Include window sizes and code compliance for egress from bedrooms, R310.
3. Identify any proposed Roof Framing Plan showing the rafters sized for supporting live and dead structural loads (Table R802.4.1(1)).

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Provide a complete plumbing plan showing code compliance, 2018 IRC.

MECHANICAL PLANS:

1. Show the HVAC system size accordance with M1401.3, M1601.1.
2. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Provide a Riser Diagram and panel schedule, NEC 225.30 and E3403.
2. Show a smoke alarm in the bedroom and outside the doorway in the immediate vicinity with an electrical circuit, R314.3.
3. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, R106.1.1.
4. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
5. Show at least one wall switch controlled light or outlet in bathrooms, hallways, stairways, attached garages, outdoor entrances or exits and all habitable rooms, E3903.3.
6. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
01/28/2025 Site Engineering REQUIRES RESUBMIT See Zoning comments
01/23/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Bobby Parsons
Zoning Section Review

PROJECT: TC-RES-0323-03970
4864 E Hawthorne Street Tucson, AZ 85711
Complete T07CM00673 finishing the 2nd floor addition (1st Review)

TRANSMITTAL DATE: 1/23/2025

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Site zoning is unable to conduct a full review with the submitted documents. Please include a site plan in your next submittal which includes the information as noted in the sample site plan. Please see https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf for reference.
2. Comment: Additional comments may be forthcoming depending on the updated plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.