Permit Number: TC-RES-0323-03906
Parcel: 131051440

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0323-03906
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/14/2023 Residential Building REQUIRES RESUBMIT PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all verification inspections.

Separate the submitted files with construction plans and support documents in different files. Place sheet numbers on each sheet of construction plans.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing dimensions of all buildings requiring a permit, R106.1.1. Show the location of all utility lines from property line to building(s) along with required alterations.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window openings in the proposed space.

STRUCTURAL PLANS:

1. Provide complete structural plans showing compliance with the IRC, R301.1. Show all proposed repairs and alterations with 2018 IRC compliance, R301.1.

SECTIONS - DETAILS:

1. Provide a structure section showing existing and proposed features including a foundation, sills, anchoring, framing, sheathing and insulation, R106.1.
2. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
3. Clarify the type and thickness of ceiling/roof insulation, R806.

PLUMBING PLANS:

1. Provide complete plumbing plans showing any changes with 2018 IRC compliance, R301.1.

MECHANICAL PLANS:

Provide equipment details showing any changes with 2018 IRC compliance including locations and sizes.

ELECTRICAL PLANS:

1. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, E3404.12.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2Provide proposed wiring details showing code compliant device locations and circuit sizes. Show circuit number and size with receptacles at all walls (within 6’ of any wall location) and lighting control at each doorway both interior and exterior.

OUTDOOR LIGHTING CODE

Provide any alterations with details showing compliant fixtures. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly).

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
05/24/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0323-03906
2003 S. Rosemont Av. – R-1
Addition & Porch Built w/o Permits (1st Review)

TRANSMITTAL DATE: May 24, 2023

Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.
1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

2. Provide complete building plans for the enclosed patio, bedroom and porch with the next submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/11/2023 Fire New Construction REVIEW COMPLETED
05/10/2023 PDSD Application Completeness Express REVIEW COMPLETED