Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0323-03905
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/26/2023 Commercial Building REQUIRES RESUBMIT Please respond to the following: 1. The roof sheeting document is corrupted (it cannot be opened), please submit a readable file. 3. Submit the Manual J, D and the Extended Rating Table information for the HVAC being proposed. Please show the location of the HVAC components on the drawing (if it is on the roof, please indicate so) 4. Add all of the information from your response document onto your drawings. Ensure that the circuit breaker number supplying the receptacle, lights, appliances, etc are indicated on the drawing. 5. Ensure that besides being Tamper Resistant, ensure that AFCI is also present where required. Locate both the Smoke Alarm and Carbon Monoxide on the drawing (label them as such). 6. We understand that you are needing to permit 4 units. As previously mentioned, each unit must have their own separate permit. This submittal will be used for Unit #8205 as permit number TC-RES-0323-03905. Please submit separate permit applications (one for each of the other 3 units). 7. Please resubmit
05/22/2023 PDSD Application Completeness REVIEW COMPLETED