Permit Number: TC-RES-0323-03885
Parcel: 123040250

Address:
2921 E ELM ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0323-03885
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2023 Site Landscape NOT REQUIRED
04/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/17/2023 Residential Building REQUIRES RESUBMIT 1. Indicate the direction of slope for the garage slab, R309.1.
2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade.
04/21/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0323-03885
2921 E. Elm St. – R-1
Detached Garage (1st Review)

TRANSMITTAL DATE: April 21, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.
1. The lot coverage calculation is not correct. Per UDC Article 6.4.3.C.1.a porches open on at least one side are not included in the lot coverage. Also, patios and sidewalks are not included, see UDC Article 6.4.3.B.

2. Per UDC Article 6.6.3.E The total gross floor area (gfa) of all accessory structures shall not exceed 50% of the gfa of the principal structure. Based on the square footages provided on the plan the proposed garage & 240 sf shed exceed the allowed 50%. There are two (2) ways to address this issue: 1) Submit for a Board of Adjustment for Variance. 2) Connect the garage to the house with a minimum 5’-0” wide porch like structure that can support a 20 lb. live load.
Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
03/27/2023 PDSD Application Completeness Express REVIEW COMPLETED
04/05/2023 Site Engineering REVIEW COMPLETED