Permit Number: TC-RES-0323-03876
Parcel: 118040180

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0323-03876
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2023 Site Engineering NOT REQUIRED
05/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/18/2023 Residential Building REQUIRES RESUBMIT TC-RES-0323-03876
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.


STRUCTURAL PLANS:

1. Provide stamped truss plans for all spans, R804. The submitted file only shows one of three spans.

SECTIONS - DETAILS:

1 Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show with dimensions the exterior wood siding, insulation, interior sheathing, and pressure treated sill anchored with ½” x 10” bolts. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.
2 The garage framed wall requires a concrete stem for achieving the 6” clearance between framing and ground (R317.1 item 5) for a sloping floor.
3 Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2. Show size and location of roof vents.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A four bedroom dwelling of 1501 – 3000 SF requires a 75 CFM continuous setting.
2. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate the mechanical plans if system calculations will be provided by deferred submittal.

ELECTRICAL PLANS:

1. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets, E3703.2 and E3901.3. Replace the undersized 15 AMP circuits with 20 AMP.
2. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
3. Garage Receptacle Location: a 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.
4. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
05/17/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T21CM00764 1716 W SAN MARCOS BL Zoning R-1 TRANSMITTAL DATE:‎May 10, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a calculated wall height of 14’-2” the required perimeter yard setback from the structure to the west property line is 9’-6”, the proposed setback is 6’-0”. A Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf If you have questions about the DDO application or process please contact Wyatt Berger at wyatt.berger@tucsonaz.gov or Georgia Pennington at georgia.pennington@tucsonaz.gov 2.COMMENT: Draw dimension and label the height of the structure measured from design grade to top of wall. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
05/17/2023 PDSD Application Completeness Express REVIEW COMPLETED