Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0323-03671
Parcel: 133200990

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0323-03671
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/13/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0323-03671 (901 N BARBARA WORTH TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated plans and calculations with a written response to each of the notated items indicating action taken.

Reinstallation needs to meet code requirements from 2018 IRC and 2017 NEC.
1. Provide a complete plan set showing reinstallation complies with all currently adopted code requirements.
2. Provide complete roof framing information for determining load carrying capacity for the roof structure. Show all load bearing locations. Demonstrate the ability for supporting the existing and additional dead load, or provide an engineer’s calculation, design and seal for verifying the truss load carrying capacity.
3. Provide two pathways, on separate roof planes from lowest roof edge and not less than 36” wide. IRC R324.6.1
4. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, IRC R301.1. An IRC PV roof uplift calculator is available on Pima County’s website. https://webcms.pima.gov/cms/One.aspx?pageId=62064
5. When applying for a permit to place equipment on existing code-compliant roofs, an allowance shall be provided for equipment weighing a maximum of 4 psf and load per attachment point of 40lbs or less. https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Development%20Services/Building/Equipment%20on%20roofs%20.pdf
6. Provide an Electrical 3-line diagram identifying each component and circuit notating sizes and installation details.
7. Show rapid shutdown complies with 2017 NEC 690.12.
8. Detail all changes being made.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov