Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2023 Site Engineering APPROVED
04/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/13/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0323-03636 (2217 S AVENIDA GUILLERMO TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated plans and calculations with a written response to each of the notated items indicating action taken.

1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. An IRC PV roof uplift calculator is available on Pima County’s website. https://webcms.pima.gov/cms/One.aspx?pageId=62064
When applying for a permit to place new equipment on existing code-compliant roofs, an allowance shall be provided for equipment weighing a maximum of 4 psf and load per attachment point of 40lbs or less. https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Development%20Services/Building/Equipment%20on%20roofs%20.pdf
2. Provide calculations showing total roof equipment weight is a maximum of 4psf and load per attachment point of 40lbs or less.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/17/2023 PDSD Application Completeness Express REVIEW COMPLETED