Permit Number: TC-RES-0323-03573
Parcel: 123130790

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-RES-0323-03573
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
04/12/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0323-03573 (2317 N HAMPTON ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated plans and calculations with a written response to each of the notated items indicating action taken.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and lines supporting the alterations, R106.1.1. Show the utility lines requiring upgrade or replacement.

ELECTRICAL PLAN:

1. Provide a complete Electrical plan showing complete scope of work.
2. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2.
3. Show the location of the panel on the Electrical Plan with clear working space compliance, E3601.6.2 & E3705.8.
4. Provide electrical load calculations for determining the service panel size, E3602.2.
5. Additional comments may be forthcoming based on information from complete Electrical plan.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov