Permit Number: TC-RES-0323-03508
Parcel: 136073910

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0323-03508
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/10/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0323-03508 (9312 E BARBARA JEAN PL TUCSON, AZ 85710)
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated plans and calculations with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, and electrical. All code references are to the 2018 International Residential Code and https://www.tucsonaz.gov/files/integrated-planning/pdsd/2018_-_IRC_Amendments.PDF and 2017 NEC. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

1. Solar and electrical equipment cannot be placed on the structure above or around the pool. Overhead electrical line/equipment separation from the pool location must be a minimum of 10 foot horizonal and 22.5 foot diagonal from the inside edge of the pool, E4203.6. Provided pictures and measurements show this required clearance cannot be achieved on this structure.
2. Solar equipment cannot be placed on an unpermitted structure. After reviewing https://pro.tucsonaz.gov/ I see no record of this metal structure receiving a permit. Apply for a separate residential building permit to bring this structure into compliance. A full set of construction plans are required as part of the permitting process. See https://www.tucsonaz.gov/pdsd/residential-permits for example plan sets.

Solar Review:
1. Roof top solar installation requires a full Plan Set and equipment spec sheets, to verify code compliance. Various code requirements include, but are not limited to, 2018 IRC Section R324 Solar Energy Systems, 2017 NEC. Articles 690, 705, 706. 310.15.
2. To continue with a solar installation permit, provide a complete Plan Set for review.