Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0323-03388
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2023 | Site Zoning | APPROVED | |||
| 03/14/2023 | Site Engineering | NOT REQUIRED | |||
| 03/09/2023 | Site Landscape | NOT REQUIRED | |||
| 04/06/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/06/2023 | Residential Building | REQUIRES RESUBMIT | 1. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. Remove "Not for Construction" from the next plan set. 2. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. 3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16. |
||
| 03/09/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |