Permit Number: TC-RES-0323-03388
Parcel: 135051080

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0323-03388
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2023 Site Zoning APPROVED
03/14/2023 Site Engineering NOT REQUIRED
03/09/2023 Site Landscape NOT REQUIRED
04/06/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/06/2023 Residential Building REQUIRES RESUBMIT 1. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration. Remove "Not for Construction" from the next plan set.

2. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation.

3. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.
03/09/2023 PDSD Application Completeness Express REVIEW COMPLETED