Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-RES-0323-03303
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/04/2023 | Residential Building | REQUIRES RESUBMIT | TC-RES-0323-03303 (945 N QUEEN AV TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. 1. Verify the water heater circuit size for serving both the WH and Dryer loads, E3702.11. 2. Use Table E3705.5.3 for sizing 15, 20 & 30 AMP branch circuit conductors and protection ratings. 3. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. 4. Provide electrical load calculations for determining the service panel size, E3602.2. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |