Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0226-01008
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/27/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Multiple meters are not permitted for distributed generation (DG) installations except as specifically required by TEP. Per TEP ESR-710 (Customer-Owned Renewable Energy Systems), DG systems are allowed only the required utility service meter and, where applicable, a single approved DG production meter. Additional revenue or utility meters for DG generation are not authorized. All PV generation must be metered and shall not be diverted by ESS or other means. 2) Please show adherence to R330.8 Protection from Impact. ESS is placed within a drivable portion of the driveway, verify the height/location of ESS if relocated. If the ESS remains in the driveway, please use of the methods depicted in R330.8.3. **All construction permitted after Jan. 1 2026 shall comply with the 2024 International Building Codes, the 2023 NEC, and all City of Tucson adopted amendments. See this link for more information. https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes ** |
||
| 02/26/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |