Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0226-01008
Parcel: 128140580

Address:
5259 E 18TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0226-01008
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comments:

1) Multiple meters are not permitted for distributed generation (DG) installations except as specifically required by TEP. Per TEP ESR-710 (Customer-Owned Renewable Energy Systems), DG systems are allowed only the required utility service meter and, where applicable, a single approved DG production meter. Additional revenue or utility meters for DG generation are not authorized. All PV generation must be metered and shall not be diverted by ESS or other means.

2) Please show adherence to R330.8 Protection from Impact. ESS is placed within a drivable portion of the driveway, verify the height/location of ESS if relocated. If the ESS remains in the driveway, please use of the methods depicted in R330.8.3.

**All construction permitted after Jan. 1 2026 shall comply with the 2024 International Building Codes, the 2023 NEC, and all City of Tucson adopted amendments. See this link for more information. https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes **
02/26/2026 PDSD Application Completeness Express REVIEW COMPLETED