Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADU v.1

Permit Number - TC-RES-0226-00849
Review Name: RESIDENTIAL ADU v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/24/2026 Addressing Validation REQUIRES RESUBMIT For any questions contact: PDSD-Residential@tucsonaz.gov

The address on the Manual J must match the address on the permit. Please resubmit the Manual J with matching permit address on every page once this initial review is complete.

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
03/02/2026 Residential Building REQUIRES RESUBMIT TC-RES-0226-00849

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

Provide a separate response letter addressing each comment with location of change on the plans.

GENERAL COMMENTS:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

SITE PLAN:

1. Each dwelling requires an appropriate source of electrical and water supply, R106.1.1. Identify the existing water supply pipe size and path to the water meter.

PLANS:

1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions.
2. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.
3. Provide a complete roof framing plan with porch beams sized with appropriate prescriptive load carrying capacity, R301.1, or provide an engineer’s sealed plan set for performance compliance consideration, R301.1.3.
4. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches is required between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing, water-resistive barrier and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
2. Show a minimum of one #4 rebar in the proposed continuous footing, R403.1. Update detail A & B on sheet S0.0.
3. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Identify the device model number providing an adjustable setting and note the minimum continuous setting. A two or three-bedroom dwelling under 1501 SF requires a 45 CFM continuous setting.
2. Provide makeup air of not less than 100 square inches where a clothes dryer is placed in a closet, M1502.6.1.

PLUMBING PLANS:

1. The Tucson Water Department limits flow rates for the water meter size in compliance with P2903.7. Show an appropriate water meter size for the additional demand. Show an appropriate yard pipe size with connection between the existing dwelling and the meter. Sheet A2 shows a ¾” size and sheet MEP-2 shows a 1” size.
2. Show the water heater rating/capacity for verifying the utility size, P106.1.1.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a service disconnect for both the primary and ADU dwelling (location site specific), E3403. Show the ADU feeder size and appropriate breaker requirement, E3602.1 & E3603.1.
2. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
3. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
4. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026. E3902.14.
5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

OUTDOOR LIGHTING CODE

1. Provide full cut-off FCO style fixtures or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining compliance within exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.
2. The simplified prescribed energy value for the ceiling is R=38, N1102.1. Update the values on sheet A6 or show overall compliance by providing a RES check calculation.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
02/24/2026 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-0226-00849
Location: 10661 E CALLE NOPALITO
Review Date: 2/24/2026
Site Engineering Comments:
1. Per the City of Tucson Inclusive Home Design Ordinance (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf, all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”. Draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in 2017 ICC A117.1 Sections 402-403, including the minimum 4ft-width, slope and composition materials.
Corey Hines
Corey.Hines@TucsonAZ.gov
03/10/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Jeffrey W. Cassidy, Planner
Planning & Development Services Department – Current Zoning Review Section

PROJECT: TC-RES-0226-00849 – Residential Building – New ADU
10661 E CALLE NOPALITO Unit 2 TUCSON, AZ 85748 (RX-1Zoning)
Site Plan Review – 1st Review

TRANSMITTAL DATE: March 10, 2026

This site is in the RX-1 Residence Zone (UDC 4.7.6). An accessory dwelling unit is a permitted use in this zone (Table 4.8-1) per use specific standards 4.9.7.B.6, .8, & .9 and 6.6.3.

The City's Unified Development Code (UDC) (Section 1.4.1.C) establishes that before the City issues any approvals or permits; we must confirm that a site complies with UDC standards. Therefore, as part of permit reviews, we review a site's permit history and compare it to aerial photography to confirm that unpermitted work has not occurred. In many cases, this does mean that a homeowner must apply for permits for unpermitted work before we can approve any new work on that site.

Plan review for the above referenced accessory dwelling unit (ADU) has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

1. COMMENT: As part of the passing of Ordinance 12219 this past December of 2025, the following landscaping is required for all new single family residential, middle housing development, and accessory dwelling units, as of January 01, 2026 per UDC 7.6.10.

A. One tree / 1,000 floor area.

B. A 5’-0” wide strip of Vegetative groundcover is required within the front yard setback per the calculation below (minus the sections that have a driveway and/or pedestrian sidewalk (from the street sidewalk to the units’ front entrance). Parcels with less than 30 lineal feet of street frontage may place the required ground cover in alternate locations indicated on the site plan.

(X Linear feet of Street Frontage) – (Y curb cut width) x (5 Foot Depth) = Z Square Feet of required vegetative groundcover.

C. Plants must be low to very low water use with a hardiness rating of 15 degrees
Fahrenheit or lower and non-invasive. Options are listed in Section 5-02.5.0 of
the Technical Standards Manual. Exceptions to these criteria or plants that are
not listed in Section 5-02.5.0 of the Technical Standards Manual, may be
approved by the PDSD Landscape Architect.

D. Required landscaping must be located as follows:

1. A minimum of fifty percent of the required canopy trees must be located within
the front yard setback area.

a. Exception: If site constraints prevent new tree placement in a front yard,
five shrubs may be substituted per required tree. Required trees must still
be placed elsewhere on the site. Shrubs used as a substitute plant material for the required tree shall range from three feet in height by three feet in width, or larger. Shrubs must follow the relevant spacings from utility lines in section 5-01.5.11of the Technical Standards Manual but can be planted one radius of their mature width from foundations, enclosed sidewalks, sidewalks, and curbs.

2. Trees may be planted at varying distances apart.

3. Required landscaping is not restricted to the first 10 feet onto the property from the existing or future right-of-way line.

4. Newly planted trees must be placed at a minimum distance from existing or proposed City of Tucson-owned or private utility-owned lines, as found in section 5-01.5.11 of the Technical Standards Manual. Tree plantings are not permitted in El Paso Gas Easements or under overhead power lines.

5. Trees shall be placed a minimum of ten feet from the center of the tree trunk to any enclosed structure.

6. Trees shall be placed a minimum of five feet from the back of the sidewalk or
curb. If this standard cannot be met, then root barriers are required and must be
illustrated on the submitted construction plans.

7. Trees must be planted in a six-to-nine-inch depressed planting area of at least
50 square feet (four-foot radius, or alternatives as proposed) and at least ten feet
away from a building foundation.

8. Existing, established trees on property, at least 4 inches trunk diameter at chest height, located at least ten feet from the foundation or with an unobstructed dripline at maturity, shall count toward this requirement. The root systems of existing trees used for this requirement must be protected from soil compaction during construction using perimeter protective fencing around the dripline. Established trees are not required to have a depressed planting area. Existing shrubs and vegetative groundcover may also be used toward the required landscaping.

C. Vegetation shall be established, maintained, and sustained throughout its life in support of the City’s tree count, climate, and walkability goals. One of the following two options may be used:

1. Drip or bubbler irrigation with backflow protection. A simple irrigation system can be part of the domestic water supply for the residence.

2. Alternate methods, such as rainwater harvesting, hand watering, and greywater systems, as proposed by the property owner and approved by the PDSD Landscape Architect.

D. Proposed landscaping and related items can be included in a residential plot plan; a
Landscape Plan is not required.

2. COMMENT: After reviewing the property documentation history in Property Research Online (PRO), zoning could not verify any permit documentation for the existing Recreational Vehicle ‘Carport’ in the southeast part of the property

Zoning will not be able to approve the permit application until the permit information is provided. If permit documentation cannot be provided, the RV Carport may be permitted on a separate permit application.

Be sure to include the height of this accessory structure and the setback dimensions from the adjacent east and south property lines on that permit as zoning suspects both standards are close to being exceeded or were exceeded.

3. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

1. Corrected building permit

2. Provide a detailed response letter (clarification narrative) with your submittal that clearly shows how you have addressed all Zoning comments.

3. Resubmit ALL documents associated with this permit (all drawings in sheet index)

4. Separate Building permit for separate accessory structure.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code
02/24/2026 PDSD Application Completeness Express REVIEW COMPLETED