Permit Number: TC-RES-0226-00537
Parcel: 128061280

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.4

Permit Number - TC-RES-0226-00537
Review Name: RESIDENTIAL ADD/ALT v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/06/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0226-00537
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2024 IRC with amendments and building ordinances for all dwellings.

A permit requires the correct application type. Request the cancellation of this application for an addition/alteration permit and apply for a new dwelling permit. This addition/alteration application may continue if cooking appliances are not included and the plans are titled as a Sleeping Quarters.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. Show Pima County assigned unit numbers at each dwelling on the site plan. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU or second dwelling with kitchen at the time of permit payment.

Provide a separate response letter addressing each comment with location of change on the plans.

GENERAL COMMENTS:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Building-Codes

1. A (detached) addition requires the removal of the kitchen. Update the plans showing a wet bar without major appliances.
2. A dwelling with kitchen requires compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

SITE PLAN:

1. Show the utility meters and lines from the utility source to the building, R106.1.1. Identify the utility lines requiring upgrade or replacement.
2. Show building square footage sizes from exterior foundations rather than interior surfaces.
3. Roof projections extending into the 6-foot fire separation distance between dwellings require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). Show the fire rated method in compliance with IBC Table 721.1(2).

PLANS:

1. An ADU requires a cool (white) roof finish (greater than 60 SRI).
2. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the living space.
3. Provide a header schedule or identify compliant header sizes supporting the roof consistent with Table 502.5(1) & R602.7(1).
4. Provide a minimum 6 mil polyethylene vapor retarder with joints lapped not less than 6 inches between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist, R506.3.3.

SECTIONS - DETAILS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).
2. Provide a wall section detail with reinforced foundations for anchoring exterior framed walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
3. Show exterior wood siding, sheathing, water-resistive barrier and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
4. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2.

MECHANICAL PLANS:

1. Show the HVAC system size for the building demand in accordance with M1401.3, M1601.1.
2. Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1.
3. Identify the device model number providing an adjustable setting and note the minimum continuous or intermittent setting for providing whole-house mechanical ventilation, R303.4; N1103.6 & M1505.4.
4. Provide makeup air of not less than 100 square inches where a clothes dryer is placed in a closet, M1502.6.1.

PLUMBING PLANS:

1. Show an individual accessible water supply shut off and water heater for the proposed building, P2903.9.1.
2. Show the water heater rating/capacity for consistence with the electrical circuit size, R106.1.1.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing a service disconnect for both the primary and detached building, E3403. Show the feeder size and appropriate breaker requirement, E3602.1 & E3603.1.
2. Provide a minimum service conductor rating of #3 copper 75 degree C for the 100 AMP feeder for an ADU dwelling unit, E3602.1 & E3603.1
3. Show a surge-protective device (SPD) as an integral part of or placed immediately adjacent to the service equipment, E3606.5.
4. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens
10. Provide GFCI protection for receptacle outlets and HVAC equipment after September 1, 2026, E3902.14.
5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.20. Add notation to plans.

OUTDOOR LIGHTING CODE

1. Show the proposed exterior fixtures as full cut-off (FCO) style for eliminating the need for an Outdoor Lighting Calculation when processing the site plan permit.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
08/21/2026 Residential Engineering REQUIRES RESUBMIT Permit Activity Number: TC-RES-0226-00537
Project: Residential Alteration/Addition – ADU
Location: 841 S VAN BUREN AV
Review Date: 8/21/2026
Reviewer: Joe Macaulay – Civil Engineer – Residential Engineering

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter review time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued. Provide a response letter addressing each comment with location of change on the plans. Submit the separate response letter and plan set files.

Residential Engineering Review Comments:
1. Project is in a Regulated Flood Zone “AE” associated with the Arcadia Wash and will require intermediate and final elevation certificates. Please include BFE and FFE on next submittal.
2. Due to the property location within floodplain limits, the new detached dwelling must be built to floodplain standards. Show the finished floor elevation (FFE) on the construction site plan (sheet AS101). Based on a calculated base flood elevation (BFE) of 2584.90-FT NAVD88, and a regulatory finished floor must be (at a minimum) FFE = 2585.90-FT NAVD88.
3. A grading permit is not required for this project, but a Drainage Statement (Standards Manual for Drainage Design and Floodplain Management Section 2.1.3), prepared by an Arizona registrant will need to be submitted with Erosion Hazard Setback requirements determined and reflected in the submitted plans.
4. The elevation of the building pad and FFE will be conducted by a registered surveyor, and the completed elevation certificates must be submitted to TE-FPU-0326-00072 for review and approval.
5. Site Engineering will be unable to approve permit TC-RES-0226-00537 until the associated grading permit is approved and issued. It is recommended that the grading permit process be started and achieve approval and issuance prior to the resubmission of this permit to ensure no project delays and review overlap.
6. The City of Tucson Inclusive Home Design Ordinance requires all new dwellings — including ADUs, single-family residences, and duplexes — to provide an accessible route connecting the public street, sidewalk, or driveway to an accessible entrance of the home. This pathway must be shown, dimensioned, and labeled on the plans. What this means in plain terms: There needs to be a clearly defined, walkable path from where a person arrives (the street, sidewalk, or driveway) all the way to a usable door of the home — one that someone using a wheelchair or mobility aid could navigate without barriers. An exterior accessible route that shall conform to 2017 ICC A117.1 Sections 402 and 403 and City of Tucson Inclusive Home Design Ordinance.
Reference: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf

Action Items — Show the following on your plans:
a. Draw and label the path as "Accessible Route"
b. Provide a minimum clear width of 4 feet with a width call-out on the plans
c. Note the proposed running slope (must not exceed 5% / 1:20) and cross slope (must not exceed 2% / 1:50)
d. Identify the accessible entrance the route leads to.

Acceptable Accessible Route compositions include:
e. Portland cement concrete (PCC)
f. Broom Finished concrete
g. Brick or unit pavers (Only if set on a stable cement base with no gaps exceeding ½”)
h. Concrete pavers on concrete base (Same joint and evenness requirements as brick)
i. Flagstone: must be mortared – loose set does not qualify
j. Any surfaces equivalent in smoothness, hardness, and durability
NOTICE: Decomposed granite (DG) is not permitted for required accessible routes, even if compacted 6. Please review and address zoning comments. Due to zoning constraints the location of the structure may change, if the structure location may change or detached ADU becomes attached, please contact Site-Engineering@tucsonaz.gov.

If you have any questions or concerns, please contact Joe Macaulay at Joe.Macaulay@tucsonaz.gov
08/10/2026 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Roxanne Johnston, Planner
PROJECT: TC-RES-0226-00537
841 S. Van Buren Av., Tucson, AZ 85711
ADU (4th Review)

TRANSMITTAL DATE: 08/10/2026

This site is located within the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.

1. Clarify what the structure is as this is unclear. The proposed structure is either an ADU/Casita or Sleeping/Guest Quarters. The differences are that ADUs are assessed impact fees as they contain a full refrigerator and stove. Additionally, these require a 4’-wide dust free ADA pathway leading from the unit to a public ROW and a separate address, such as 841 S Van Buren Av, Unit 2.” Sleeping Quarters do not contain a stove, may only contain an under the counter refrigerator, requires no new landscape, no ADA pathway, no separate address, and are not assessed impact fees. Sheet A102 shows a full refrigerator, but no stove. The plans are labeled “Casita” throughout.

2. Provide a Full site plan that meets the requirement for a Zoning review found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Site-Plan-Examples

Most missing information from the site plan (Sheet AS101) includes the following, but again, it is important to follow the above link to ensure the success of the reviews:

a. Name and Total Lot Coverage as required by Unified Development Code (UDC) 6.4.3.B. Provide a table with this information on Sheet AS101. This includes the total of all enclosed buildings and vehicle use areas divided by the lot’s square footage. The remaining figure should be a percentage not to exceed 70%.
b. Label the square footage of the residence and the proposed ADU.
c. The correct side and rear setback information as shown in Table UDC Table 6.3-2.A. Specifically, 5’ to the side and rear lot lines. The front setback remains 20’ as shown on Sheet AS101.
d. Name of owner
e. Zoning classification (R-1)
f. North arrow
g. Location of existing and proposed utility lines. Show the sewer main connection.
h. Show the 5’ utility easement along the south property line.
i. Dimension the driveway.

3. Provide a landscape plan. It is not necessary to hire a landscape architect. Here is the link for the landscape requirements: https://middle-housing-cotgis.hub.arcgis.com/pages/Residential-Landscaping-Code Essentially, if no existing trees in the front yard, 1 tree is required for the ADU. The required groundcover square footage, which may consist of shrubs, is calculated by the width of the property line at the street minus the driveway width, multiplied by 5. List the plant and tree names, even if existing, location and preferred watering methods. All new trees shall not be planted within 10’ of a foundation nor 5’ from utility lines and sidewalks.

4. With the next resubmittal, provide the following:
a. Revised site plan
b. Construction documents
c. Response letter to all staff comments explaining how the comments have been addressed.

5. Please note the floorplan on Sheet A102 shows a full refrigerator but no stove. If the intention is for an ADU (a Casita is considered the same thing), then impact fees will apply. If ‘Sle The Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted for the next review.

The City of Tucson Unified Development Code may be accessed here: www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .

If you have any questions about this transmittal, please contact Roxanne Johnston at roxanne.johnston@tucsonaz.gov
08/06/2026 PDSD Application Completeness Express REVIEW COMPLETED