Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0225-00992
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/26/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 03/26/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/21/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Permit Review TC-RES-0225-00992 (7462 E CALLE MANAGUA TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide ESS disconnecting means in compliance with 706.7. Disconnecting means shall be within sight of the ESS. 2. Provide a PCS warning label detailing the PCS settings and current limits. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/22/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |