Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0225-00783
Parcel: 136203080

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0225-00783
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2025 Site Engineering - Standard NOT REQUIRED
03/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/12/2025 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT Permit Review TC-RES-0225-00783 (8135 E ESCALANTE RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide a Grounding Electrode System at the detached structure per NEC 690.47.
2. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure. Show grounding details for the mounting equipment and metal support frame, NEC690.43.
3. Where live parts of electrical equipment are operating at 50 to 1000 volts, such equipment shall be guarded against accidental contact by approved enclosures or other approved means, NEC110.27(A).

4. Provide structural sheets and calculations Sealed and signed by an Arizona registered Engineer.

Note any special inspections required on the plans and calculations submittals.
5. Provide a Special Inspection Certificate, if required, with Parts A and B completed. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/18/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-RES-0225-00783
8135 E ESCALANTE RD TUCSON, AZ 85730
Residential – Ground Mounted Solar (1st Review)

TRANSMITTAL DATE: 03/18/2025


This site is zoned O-3 (UDC Section 4.7.15).


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised plans, as noted in the comments below, along with a detailed letter indicating responses to the review comments.

01. COMMENT: Provide perimeter yard setback dimensions from the proposed solar unit to the applicable property lines.

For questions regarding Zoning comments, please contact me at: Krista.Hansen2@tucsonaz.gov
02/12/2025 PDSD Application Completeness Express REVIEW COMPLETED