Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0225-00727
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/07/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Permit Review TC-RES-0225-00727 (5532 E 7TH ST TUCSON, AZ 85711) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide a basic floor plan and Show the location of the sub-panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A). 2. Show the door swing of the sub-panel. Clear working space must be maintained from the floor and for the dimensions in 2017 NEC 110.26(A). (no shelving or storage in this area). 3. Panelboards shall not be located in the vicinity of easily ignitable material, such as in a clothes closet, NEC 240.24(D). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |