Permit Number: TC-RES-0225-00714
Parcel: 125150920

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0225-00714
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/07/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0225-00714 (40 E PLAZA DEL ENCANTO TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Verify the length measurements from the meter to the farthest attached appliance. The measurements provided from the meter to the individual furnace is 124’.
2. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Table G2413.4(7) Polyethylene Plastic Pipe. Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.
3. The 35’, 1 ¼” segment is undersized for the given length (124’) and total demand (405,000 btuh). This segment requires a minimum 1 ½” BIP pipe. Table G2413.4(1) (Metallic Pipe).
4. The 89’, ¾” segment to the individual furnace is undersized for the given length (124’) and demand (100,000 btuh).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/07/2025 PDSD Application Completeness Express REVIEW COMPLETED