Permit Number: TC-RES-0225-00685
Parcel: 140380500

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0225-00685
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2025 Site Engineering - Standard NOT REQUIRED
03/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/17/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0225-00685
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

PLANS:

1. Show the functional name of each existing and proposed rooms, R106.1.1. Existing bedrooms with removed windows must show code compliance for egress, R310. Include any alteration of door or window openings between existing and proposed rooms.
2. Provide a Roof Framing Plan showing the rafters sized for supporting live and dead structural loads (Table R802.4.1(1)).
3. Provide a Roof Framing Plan with dimensions showing the beams sized for supporting live and dead structural loads (Table R602.7(3)).

SECTIONS - DETAILS:

1. Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
3. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Show any additions and alterations.

MECHANICAL PLANS:

1. Show the HVAC system size for the proposed rooms in accordance with M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Show a smoke alarm in the bedroom and outside the doorway in the immediate vicinity with an electrical circuit, R314.3.
2. Designate the circuit number at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, R106.1.1.
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
4. Show at least one wall switch controlled light or outlet in bathrooms, hallways, stairways, attached garages, outdoor entrances or exits and all habitable rooms, E3903.3.
5. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
03/18/2025 Site Zoning - Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0225-00685 - CE-VIO1124-04586
6717 S BURCHAM AV. – R-1
Permit unpermitted additions and structures (1st Review)

TRANSMITTAL DATE: March 1782025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. Complete building plans are required for all new additions, enclosures, etc. that are attached to the main dwelling. The 400 sq. ft. carport requires complete building plans.

2. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Plan-Examples/Plot-Plan-Example, to include but not limited to:
a. The lot coverage calculation is not correct. Per UDC Article 6.4.3.C.1.a Roofed areas, porches, open on at least one side and walkways are not included in the calculation.
b. The east & west property dimensions are not correct and should be 79’.
c. The distance from center line of the street to the west property line is not correct and should be a total of 30’-0”.
d. Per the Littletown No 2 final plat there is a 5’ utility easement that runs along the east property line. Show this easement on the plan.
e. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10’, 1”=20’.

3. Based on aerial photos the “EXISTING SIDE PORCH” shown on the plan shows up sometime after 2005. Zoning was not able to find approved permit documents for this porch. Either provide approved documents or include the porch in this permit.

4. Provide wall heights for the southern walls of the “NEW CARPORT” & “STORAGE” shown along the south property line so that perimeter yard setback requirements can be determined. Wall height is a measurement from design grade to the highest point of the wall, UDC Article 6.4.5.B & Figure 6.4.5-A. The minimum perimeter yard setback for an interior property line is 6’-0’, UDC Table 6.3-2.A. The carport and storage do not meet the minimum setback. At a minimum a neighbors setback waive is required to reduce the required 6’-0” perimeter yard setback. To secure this neighbor’s setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
If you are not able to secure the required waiver a Design Development Option (DDO) will need to be submitted and approved prior to approval of this permit. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov”.

5. Provide building heights for the “NEW CARPORT”, “STORAGE” & “RAMADA” shown on the plan. Building height is the vertical distance measured from the design grade elevation to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge ) of the highest gable of a pitched or hipped roof, except as follows. See UDC Article 6.4.4.A & Figure 6.4.4-A.


The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/19/2025 PDSD Application Completeness Express REVIEW COMPLETED