Permit Number: TC-RES-0224-01211
Parcel: 133380800

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0224-01211
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2024 Site Zoning APPROVED
05/03/2024 Site Engineering NOT REQUIRED
05/08/2024 Site Landscape NOT REQUIRED
05/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/05/2024 Fire New Construction PENDING ASSIGNMENT
04/23/2024 Residential Building REQUIRES RESUBMIT TC-RES-0224-01211 2nd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Separate the submitted pages with construction plans and support documents (response letter) in different files.

STRUCTURAL PLANS:

1. Provide a complete roof framing plan showing the support post locations with beam span dimensions, R301.1.

SECTIONS - DETAILS:

1. Show wall sheathing and sill plate with a 6” clearance above the ground, R317.1 item 5. Show the foundation with a minimum 12” depth below grade, R403.1. Garage walls should be supported with a stem foundation because the garage floor level is sloping. Remove the incorrect 1’-4” dimension. Update detail F-2 and F-3 sheet A-2.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
04/05/2024 PDSD Application Completeness Express REVIEW COMPLETED