Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/13/2025 Light Residential Building Review (OIP) REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).
1. On page PV-03 there is no conductor size for the #5 call out. Please add to plans
2. On page PV-03 the Combiner appears to have 1 extra 20 amp fuse that is not needed as there are only 3 strings listed. Please review and revise.