Permit Number: TC-RES-0224-00918
Parcel: 112071390

Address:
2709 E GRANT RD

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.1

Permit Number - TC-RES-0224-00918
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/03/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0224-00918 (2709 E GRANT RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Update the panel schedule to show the wire size and OCPD of each circuit, E3702.2.
2. Designate the circuit number (that correlates to the panel schedule) at the location of each receptacle, switch, or utilization equipment, E3404.12. Some of the notations are blurry and not legible.
3. Show a minimum of two 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3. GFCI protected, E3902.6. >>> Plans show only one 20A GFCI kitchen circuit.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov