Permit Number: TC-RES-0224-00903
Parcel: 10714046B

Address:
350 E JACINTO ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0224-00903
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2024 Site Engineering NOT REQUIRED
03/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/01/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0224-00903 (350 E JACINTO ST TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. After a review of aerial views(https://maps2.tucsonaz.gov/Html5Viewer/?viewer=maptucson#) of the property, it appears that PV modules are mounted on an unpermitted carport structure on the east side of the building. Searching city records through PRO (https://pro.tucsonaz.gov/address_search/) found no permit history for this carport. Either provide completed permit and inspection documentation, apply for and complete permit review and inspections for the structure or remove the PV modules from the unpermitted structure.
2. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf
3. Non-listed equipment for mounting and attachments to the roof must include a design and seal by an Arizona Registrant (S-5!).
4. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/15/2024 PDSD Application Completeness Express REVIEW COMPLETED