Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0224-00810
Parcel: 118041120

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0224-00810
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/12/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0224-00810 (1272 S SAN ANTONIO DR TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Provide a complete gas piping template showing the connection from the meter to all gas appliances, G2401.1, R301.1: Include pipe size, type and length. Provide appliance demands, G2413.4.1. It appears that the provided gas pipe lines are undersized.

2. Size the pipe based on the length from the meter to the farthest attached appliance and max total Branch demand of all attached appliances using Table G2413.4(1) (Metallic Pipe) (Table G2413.4(7) (Polyethylene Plastic Pipe)), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/12/2024 PDSD Application Completeness Express REVIEW COMPLETED