Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.3
Permit Number - TC-RES-0224-00789
Review Name: RESIDENTIAL SOLAR v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/16/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1) Show all combiner circuits, show 20-amp breakers for each circuit. 2) Show PV backfeed breaker at main panel sized for both existing and new PV load (75 amps). 3) Show conductor #4 sized for both the existing and new PV. 4) Show interconnect compliance at the sub panel per NEC 705.12(B)(2)(3) 5) Make sure components 6 & 7 are sized for 75 amp. Building_Official@tucsonaz.gov |
||