Permit Number: TC-RES-0224-00755
Parcel: 10821025B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0224-00755
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/08/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0224-00755 (1511 E LIMBERLOST DR TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. The ¾” pipe from the 1” junction to the furnace is undersized. (see 8’ segment). Minimum size required is 1” BIP.
2. Size the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe), Note: The length is measured from the meter to the furthest attached appliance for all sizing, G2413.4.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/08/2024 PDSD Application Completeness REVIEW COMPLETED