Permit Number: TC-RES-0224-00625
Parcel: 123041330

Address:
2900 E SENECA ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0224-00625
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/02/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0224-00625 (2900 E SENECA ST TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Update the panel schedule showing panel size, circuit numbers, ampacity, wire size and general description for the 2 new circuits, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2.
2. Provide the tankless water heater manufacturer’s spec sheet to verify the water heater circuit size for serving the load, E3702.11.
3. Provide a floor plan showing the location of the water heater and the range. Is the existing range a gas fired? If so, note on the plans that the gas line will be permanently capped.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
02/02/2024 PDSD Application Completeness Express REVIEW COMPLETED