Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-RES-0223-03097
Parcel: 121114420

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0223-03097
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/18/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0223-03097 (4957 E BELLEVUE ST TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. OCPD for copper conductor may not exceed 50 A for an 8 AWG conductor, NEC Table 310.15(B)(16) 75 degree C, NEC 230.90(A). The conductor tagged #4 on page PV-4.0 is undersized for the 60A PV Breaker in the ConnectDER Meter Adapter.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/07/2023 PDSD Application Completeness REVIEW COMPLETED