Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-RES-0223-03094
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/24/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0223-03094 (5934 S MORRIS BL TUCSON, AZ 85706) PLUMBING Plans: 1. Note and specify all piping materials and sizes, P2609. Both materials used and the size of pipe are missing. Provide updated plans based on the notes below. 2. Provided gas piping plan is incomplete. Submit new and complete gas piping plan as demonstrated in the sample plan: https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf See also: https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf 3. Provide total demand of all connected appliances. 4. Use G2413.4.1 and G2413.4.2 to determine the required developed length. (Total length from meter to furthest attached appliance.) 5. Use Table G2413.4(1)(Metallic pipe) to calculate correct required pipe size for replaced segment. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/03/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |