Permit Number: TC-RES-0223-03078
Parcel: 140401890

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0223-03078
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/10/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0223-03078

Review Notes to be addressed in resubmitted plans and revision letter.
1. Sheets PV-4 and PV-4A show the existing system’s output amps as 0.09A. See Backfeed Breaker Sizing table. Verify and correct. (Existing Solaredge SE5000H-US has an output current of 21A).
2. Sheets PV-4 and PV-4A show the PV Breaker in the MSP as 25A. Corrections from Note #1 will require updating this detail.
3. Sheets PV-4 and PV-4A show a New 30A Rated Utility DG Disconnect. Based on corrections from Note #1, this device will need to be updated to an appropriate Amp rating.
4. Sheets PV-4 and PV-4A show a 20A OCPD for the existing system located in the N 100A Dedicated Load Center. Provided spec sheets show an output current of 21A for the existing Solaredge SE5000H-US. Update and correct.
5. Sheet PV-5, Wire Schedule will require updating based on corrections from Notes #1 - #4 (Rows 5-8).
6. If the Existing system is non-functional, as a 0.09A output current would indicate, state this non-functionality clearly on the plans and in the revision letter.
7. Further comments may be forthcoming based on updated information, details and plans.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/07/2023 PDSD Application Completeness Express REVIEW COMPLETED