Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0223-03078
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/10/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0223-03078 Review Notes to be addressed in resubmitted plans and revision letter. 1. Sheets PV-4 and PV-4A show the existing system’s output amps as 0.09A. See Backfeed Breaker Sizing table. Verify and correct. (Existing Solaredge SE5000H-US has an output current of 21A). 2. Sheets PV-4 and PV-4A show the PV Breaker in the MSP as 25A. Corrections from Note #1 will require updating this detail. 3. Sheets PV-4 and PV-4A show a New 30A Rated Utility DG Disconnect. Based on corrections from Note #1, this device will need to be updated to an appropriate Amp rating. 4. Sheets PV-4 and PV-4A show a 20A OCPD for the existing system located in the N 100A Dedicated Load Center. Provided spec sheets show an output current of 21A for the existing Solaredge SE5000H-US. Update and correct. 5. Sheet PV-5, Wire Schedule will require updating based on corrections from Notes #1 - #4 (Rows 5-8). 6. If the Existing system is non-functional, as a 0.09A output current would indicate, state this non-functionality clearly on the plans and in the revision letter. 7. Further comments may be forthcoming based on updated information, details and plans. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/07/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |