Permit Number: TC-RES-0223-03041
Parcel: 132180490

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0223-03041
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/05/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0223-03041 (1117 E OKLAHOMA ST TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken.

1. Provide Main Service Panel (MSP) taps in compliance with NEC 705* (NEC 705.12) 705.12(B)(2)(3) b Busbars.) 120% bus bar rule. Page # PV 3 and PV 4, Interconnection table shows an allowable backfeed of 50A.
2. Provide Sub Service Panel (MSP) taps in compliance with NEC 705* (NEC 705.12) 705.12(B)(2)(3) b Busbars.) 120% bus bar rule. Page # PV 3 and PV 4, 100A bus rating with 70A Solar backfeed.
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/07/2023 PDSD Application Completeness Express REVIEW COMPLETED