Permit Number: TC-RES-0223-03025
Parcel: 133261500

Address:
8128 E 4TH PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0223-03025
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/29/2023 Residential Building REQUIRES RESUBMIT TC-RES-0223-03025

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Clarify if the structure is a sleeping quarters (without kitchen) or an Accessory Dwelling Unit (ADU) which requires many alterations for compliance.

An independent dwelling (ADU) requires fire spread and utility (electrical & water) separation.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319.

An impact fee payment is required for an ADU.

GENERAL COMMENTS :

Provide a complete

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Each dwelling requires an independent electrical service and water supply shut off devices. Identify the utility lines requiring upgrade or replacement.

PLANS:

1. Provide a roof framing plan with appropriate load bearing foundations for each wall type, R106.1.1.

SECTIONS - DETAILS:

1. Provide a wall section showing one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).
2. Provide a wall section showing exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Show an individual water heater for each dwelling unit, P2801.1.
2. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.
3. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A one bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.

ELECTRICAL PLANS:

1. Provide a Riser Diagram showing service disconnect of either dwelling without service disruption of the other dwelling, NEC 225.30 and E3403.
2. Show locations of each smoke alarm, R314.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.
5. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
03/22/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0223-03025
8128 E 4th Pl. – R-1
Attached ADU (1st Review)

TRANSMITTAL DATE: March 22, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) w/ an Accessory Dwelling Unit is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9 & 6.6.3.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

2. Clarify what the “(2) 677 sqft” rectangle is that is shown on the “Prior” & “New” Site Plan.

3. The Gazebo shown on the plan shows up on aerial photos sometime after 2012. Zoning was not able to find approved permit documents for this structure. As the gazebo is greater than 200 sq. ft. a building permit is required. As this structure does not appear to meet perimeter yard setbacks to the south, no setback dimension provided, and to the west, 3’-9” at a minim a neighbor’s setback waiver will be required to permit this structure. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). As no height is provided required perimeter yard setbacks cannot be determined. To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the property owner(s) of 8128 E 4th Pl. & 8133 E Baker Dr.:
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________

4. The east/west property dimension is not correct.

5. Clearly demonstrate on the plan how the requirements of UDC Articles 6.6.3.B.2 & .3 are met.

Additional comments may be forth coming once the above comments are addressed.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov